Factory-made building panels with two skins of pre-painted steel bonded to an insulating core of polyisocyanurate (PIR), polyurethane (PUR), mineral wool or expanded polystyrene. One panel forms the wall or roof, its insulation and its finish, so sandwich panels are the usual envelope for warehouses, factories, cold stores and clean rooms in the Gulf.
Also called
Insulated panels
Composite panels
PIR panels
PUR panels
PU panels
Rock wool panels
Mineral wool panels
Cold room panels
EPS panels
AR
الألواح المعزولة (الساندويتش بانل)
ZH
夹芯板(彩钢夹芯板)
DE
Sandwichelemente (Sandwichpaneele)
FR
Panneaux sandwich
ES
Paneles sándwich
IT
Pannelli sandwich
TR
Sandviç panel
RU
Сэндвич-панели
Main formsRoof panels (trapezoidal outer skin), wall panels (flat or micro-profiled, exposed or hidden fix), cold-store panels
Typical sizesPanel thickness 40–200 mm (50–100 mm common); cover width about 1,000–1,150 mm; lengths to order, often up to 12–16 m
Main standardsEN 14509, EN 13501-1, EN 13501-2, FM 4880 / FM 4881; skins to EN 10169 / EN 10346
Key gradesSkins 0.4–0.7 mm PPGI or PPGL (S250GD–S350GD) · cores PIR, PUR, mineral (rock) wool, EPS
Typical usesWarehouse and factory walls and roofs, cold stores and freezers, clean rooms, site offices, data centres
Overview
Most metal-faced sandwich panels are made on continuous lines: two coils of pre-painted steel are profiled, the liquid PUR or PIR chemicals are foamed between them and cure into a rigid core bonded to both skins, and the panel is cut to length. Mineral wool panels are made by bonding lamellas of rock wool between the skins with adhesive. The skins carry the bending loads and the core carries shear, so a lightweight panel spans several metres between purlins or girts.
The core sets the panel's behaviour. PUR and PIR give the best insulation for the thickness (thermal conductivity about 0.020–0.024 W/mK), so they dominate cold stores and air-conditioned buildings; PIR has better fire behaviour than PUR. Mineral wool is non-combustible and is used where fire performance is required — fire walls, high-risk buildings — at the cost of greater thickness and weight for the same insulation. EPS is cheap and light but combustible and is increasingly restricted.
Fire safety of building envelopes has become a major regulatory issue since a series of façade fires. In the UAE, the Fire and Life Safety Code issued by Civil Defence sets requirements for external wall materials, and Saudi Arabia applies the Saudi Building Code's fire provisions; projects typically require panels that are tested and approved for the specific use, for example classified to EN 13501-1 or approved to FM 4880 / 4881. Approval requirements change and differ by authority, so the current rules of the authority having jurisdiction must be checked for each project.
Sandwich panels are produced in many plants across the GCC, and are widely used for logistics warehouses, factories, cold chains for food and the region's many temporary and modular buildings. In the Gulf climate, white or light-coloured outer skins, good joint sealing and attention to condensation in cold stores matter as much as the core thickness.
Forms & sizes
Roof panels
Trapezoidal outer skin with 3–5 ribs, lining skin inside; side-lap joints; 40–150 mm cores
Wall panels
Flat, micro-rib or striated skins; exposed-fix or concealed-fix tongue-and-groove joints
Core type and thickness, and the required U-value or thermal resistance.
Fire requirements of the project and the authority: reaction-to-fire class, fire resistance, and the test reports or approvals that prove them for the exact panel.
Skin steel, thickness and coating on each side, paint system and colour.
Panel profile, joint type (exposed or concealed fix), lengths and the load-span table for your wind loads and purlin spacing.
Flashings, sealants, fixings and installation guidance from the same supplier.
CE marking or declaration of performance to EN 14509 where applicable, and the warranty terms.
Quality checks
Check core type and thickness on a cut panel and against the labels and approvals.
Look for delamination (skin not bonded), voids in the foam, dents and scratches.
Check skin thickness, colour and protective film; remove the film soon after installation.
Check length and squareness, and that joints fit; store panels dry, supported and sloped.